DHA Lahore · Building Control

DHA Lahore Building Byelaws and House Map Approval Process

Clear spaces, covered area, height, porch, basement and fire safety limits for every residential plot size in DHA Lahore — each figure cited to its regulation number and printed page, so you can check it against the source yourself.

Source edition
Building Control 2026Construction & Development Regulations 2014
Issued by
Defence Housing Authority LahoreBuilding Control Directorate
Covers
5 Marla to 2 KanalAll phases
Last reviewed
August 2026Next review: December 2026

In short

The DHA Lahore building byelaws are the Defence Housing Authority Construction & Development Regulations 2014, issued by the Executive Board of Defence Housing Authority Lahore and published in the Building Control 2026 edition. They set clear spaces, covered area, height, plinth, boundary wall and basement limits for every residential plot size in DHA Lahore. Before any construction, an owner must obtain written approval of the building plan from the DHA Building Control Directorate. Construction without an approved plan is not permitted and is liable to demolition.

Regulations 1, 21 and 22, printed pages 5 and 21.

Which Edition of the DHA Lahore Byelaws Applies

The document in force is titled “Byelaws — Construction & Development, Building Control 2026”, published by Defence Housing Authority Lahore. Inside it, Regulation 1(a) states that the regulations are formally called the Defence Housing Authority Construction & Development Regulations 2014. Both names refer to the same instrument: the 2014 regulations as consolidated, amended and reprinted in the 2026 edition. Anyone quoting a “2022 revised byelaws” figure to you is quoting a superseded print.

The regulations extend to the specified as well as the notified area of DHA Lahore and are read together with the DHA Projects / Joint Venture Regulations 2004.

Regulation 1(a), (b) and (c), printed page 5.

Under Regulation 70 the Executive Board is competent to amend these regulations at any time, and amendment expressly includes addition, deletion, substitution and modification. Figures change between editions. Every number on this page is reproduced from the edition named above and was checked against the printed page. Before you submit, confirm the current edition and any subsequent amendment with the DHA Building Control Directorate. This page is a reference, not a substitute for that confirmation, and it is not legal advice.

Regulation 70, printed page 43.

If your house was approved under an earlier edition

Regulation 1(d) is one of the most useful clauses in the document and one of the least known. Where a house or building has been constructed in accordance with drawings approved under previous byelaws, rules or regulations, and that construction contradicts the present regulations, the violation may not be objected to and the completion certificate is issued accordingly.

In plain terms: a compliant house does not become non-compliant because the byelaws changed after it was approved. What matters is the edition in force when your drawing was approved.

Regulation 1(d), printed page 5.

The DHA Lahore House Map Approval Process, Stage by Stage

Eight stages, from drawing preparation to completion certificate. Each stage below names the regulation that governs it.

  1. Drawings prepared and signed by a registered architect

    The building plan is submitted to the Building Control Branch signed by a registered architect. The regulations define a registered architect as an architect registered with the Pakistan Council of Architects & Town Planners (PCATP) and also registered with the Authority. Registration with PCATP alone is not sufficient. This is the first point at which a plot owner cannot proceed alone, and it is the point most often discovered late.

    Regulation 15 opening paragraph, printed page 18. Definition 76, printed page 10.

  2. Assemble the document set

    Regulation 14 lists the documents that must accompany the application. This is separate from, and additional to, the drawing content requirements in Regulation 15.

    • a1 × tracing cloth plus 5 × ammonia prints of architectural drawings
    • b2 × structure drawing prints on tracing cloth
    • c2 × MEP drawings on ammonia prints
    • d2 × fire / safety drawings on ammonia prints
    • eElectrical engineer’s certificate
    • fMechanical engineer’s certificate
    • gArchitect stability certificate
    • hStructure stability certificate
    • iForm A & B (Cantonment Board)
    • jPhotocopy of allotment / transfer letter
    • kPhotocopy of site plan issued by Building Control Directorate in the name of the current owner
    • lPhotocopy of owner’s CNIC
    • mOriginal paid challan of drawing scrutiny / vetting charges (challan form from the Front Desk)
    • nSoft copy of architectural drawing in AutoCAD format with 3D view, on CD
    • oIrrevocable general undertaking on Rs 300 stamp paper (specimen on the DHA website)
    • pOriginal soil testing / geotechnical report — validity one year
    • q2 × 3D views provided with architect’s seal

    Regulation 14, printed page 17.

    Plan for item (p) early. The geotechnical report is valid for one year and is required at submission. It has to be commissioned, the field work carried out and the report issued before the application can be lodged. An owner who leaves it until the drawings are ready has added weeks to the programme for no design reason, and a report obtained more than a year before submission has to be redone.

  3. Drawing content

    Regulation 15 sets out what the drawings themselves must show, in twenty-two lettered requirements. The ones that most often decide whether a set is complete:

    • External dimensions of the main building with extended portions; internal dimensions of all rooms; positions and dimensions of all projections beyond the walls.
    • A schedule of open, covered and permissible areas — the arithmetic that proves the design sits inside the covered area limits.
    • Thickness and composition of all beams, columns, lintels and other RCC components; schedule of steel reinforcement.
    • Level and width of foundations and the level of each floor, referenced to the level of the centre of the road on which the building abuts.
    • Overall height of the building including overhead water tank, staircase, machine room for lift and parapet walls.
    • Cross-section of the boundary wall towards the road.
    • Water supply layout with underground and overhead tank details, and sewerage layout with septic tank, sump, collection chamber and cross-sections — both in the MEP drawings.
    • Plan and elevation at a scale of 1 inch = 8 ft. Cross-sections and longitudinal sections at 1 inch = 4 ft.
    • A certificate from the registered architect confirming that all components of the building have been designed by them.
    • A structural stability certificate from a registered structural engineer. For commercial buildings, from a PEC-registered consulting engineer (M.Sc Structure) with minimum five years’ experience, for multi-storey buildings.
    • The applicant must on demand produce all necessary details of the structural designs and calculations.

    Regulation 15(a) to (v), printed pages 18–19.

  4. Scrutiny — 21 working days

    The Authority scrutinises the drawings and documents within 21 working days, for all residential and commercial buildings. Five sets are scrutinised: building plans, structural drawings, fire protection drawings, MEP drawings and 3D views.

    Regulation 16(a), printed page 19.

    Note what that list means: fire protection and MEP are not post-approval fit-out matters. They are scrutinised sets, required at submission, and an incomplete or absent set is an incomplete application.

  5. If the submission is returned

    The Authority may reject the application and return the drawings and documents where plans are illegible, ambiguous or in contravention of the rules and regulations. When it does, it gives reasons in writing and returns the set together with guidelines for resubmission. The Authority also reserves the right to reject plans, or to suggest modifications, where the design does not contravene the regulations but is in its view injurious to the health, welfare, safety and comfort of residents.

    Regulation 16(b) and (c), printed page 19.

    The clause that changes the economics: on resubmission the application is deemed to be a fresh application, and a period of 21 working days commences again from the date of resubmission.

    Regulation 16(d), printed page 19.

    This is why compliance checking belongs at concept stage rather than at submission stage. A clear space or covered area assumption that is wrong at concept costs a redraw. The same assumption discovered at scrutiny costs the redraw plus a fresh 21 working day clock — and it does so at the point in the programme where the owner has usually already agreed a start date with a contractor.

    Has your map been returned with observations? Send the plot details and the observation list and we will tell you what has to change.

    Discuss my resubmission
  6. Collection of approved documents

    After approval, the applicant collects the documents in person or through attorney. That second route is what makes remote approval workable for an owner living abroad.

    Regulation 16(e), printed page 19.

    One clause worth reading carefully: any oversight in the scrutiny of documents and drawings at the time of approval does not entitle the person to violate the regulations or to claim damages. If a violation later comes to the Authority’s knowledge, it is pointed out to the applicant, who must rectify it in the given time at their own risk and cost. An approval stamp is not a warranty that the drawing is compliant.

    Regulation 16(f), printed page 19.

  7. Verification at five construction stages

    Every registered person is bound to get construction verified from the Building Control Directorate at five stages, in order to avoid violations:

    Reg 18 — verification stages
    StageWhen
    1When the layout has been completed, before starting the work
    2On construction of the main building up to DPC level
    3Upon raising the 1st floor structure by 1 foot from the ground floor roof slab
    4At post grey structure
    5On final completion before occupation, at the time of getting the sewer connection opened

    Regulation 18(a) to (e), printed page 20.

    The note attached to Regulation 18 matters as much as the list. Permission granted after the inspection of any stage does not relieve the registered person from the responsibility of keeping the construction free of all violations. Separately, authorised officers may inspect the premises at any time, without prior notice. If a person denies inspection, the Authority may serve a notice and then disconnect water supply and sewerage services, and may impose violation charges.

    Regulation 18 Note and Regulation 19(a), printed page 20.

  8. Completion certificate

    On completion the member contacts the Authority for sewer and water connections before occupying the building. Occupying without those connections is liable to fine. The application requires two ammonia copies of the approved drawing and two photographs of 6 inch × 4 inch showing the front elevation — and two more showing the side elevation on a corner plot — with the requisite fee.

    The certificate is normally issued within 20 days if no violation is observed and construction is found to be in accordance with the approved drawing. The date of sewer opening is treated as the date of completion. The member is bound to obtain it within 3 years of approval of the drawing, failing which a fine is levied monthly.

    Regulation 48(a) to (e), printed page 34.

The deadlines that run in the background

Statutory deadlines
DeadlineWhat it requiresRegulation
3 years from possessionCommence construction within 3 years from the date the area was opened for possession or construction by the Authority, failing which a non-construction penalty is payable as prescribedReg 17(a), p19
2 years from approvalComplete the building within 2 years reckoned from the date of approval of the drawingReg 17(b), p19
2 years drawing validityThe drawing remains valid for two years from approval. On lapse, fresh approval must be obtainedReg 17(c), p19
3 years to completion certificateObtain the completion certificate within 3 years of approval of the drawing, failing which a fine is levied monthlyReg 48(e), p34
Purchasers and transfereesA purchaser or transferee, including Hibba, has three years for construction from the date of opening of possession. Sold within 3 years: penalty not levied until three years from opening of possession or 24 months from transfer, whichever is later. Sold after three years: 24 month grace period, penalty levied from date of transferReg 13(d)–(e), p17
ShuhadaNon-construction penalty is not imposed on Shuhada. Legal heirs are considered in the same status as the deceased memberReg 13(f)–(g), p17

One further clause interacts with the drawing validity period. A site once excavated must not be kept open and idle beyond the validity period of the building plan; if it is, the Authority will not revalidate the plan. A building once started may not be left incomplete or abandoned for an indefinite period — in such cases the building plan becomes invalid for starting reconstruction.

Regulation 43(a) and (b), printed page 32.

Clear Spaces (Setbacks) by Plot Size

A specified clear space is defined as the minimum part of a plot which is to be left completely and compulsorily open to sky, over which no structure — even temporary — or any integral part of the building is permitted.

Definition 91, printed page 11.

Find the limits for your plot

Select your plot size. The table below highlights to match.

Plot size
Front
15′-9″incl. boundary wall
Rear
5′-4½″incl. boundary wall
Each side
5′-4½″incl. boundary wall
First floor
80%of ground floor

Maximum residential height is 39 ft from the crown of the road, for all phases and all plot sizes.

Check this against my plot

The clear spaces below are minimums and, critically, they are stated as including boundary walls. Read the note beneath the table before using any of these figures in a design.

Reg 22(a) — minimum clear spaces, including boundary walls
Plot sizeFront RearSide (each)
2 Kanal — 75′×120′20′-9″8′-4½″5′-4½″
2 Kanal — 100′×90′15′-9″8′-4½″5′-4½″
1 Kanal15′-9″5′-4½″5′-4½″
10 Marla10′-9″5′-4½″5′-4½″
9 Marla9′-0″5′-4½″4′-9″
8 Marla8′-0″4′-0″4′-0″
7 Marla7′-0″3′-0″3′-0″
5 Marla5′-0″3′-0″3′-0″

Regulation 22(a), printed page 21. The published table lists two SIDE columns; for 2 Kanal and 1 Kanal both are populated at 5′-4½″, and for 10 Marla and below a single dimension applies to each side.

What “including boundary walls” changes for you

The clear space is measured to include the thickness of the boundary wall, not from its inner face. A boundary wall is 9 inches thick and, where it is a common wall, is built using 4½ inches of the adjoining plot — so 4½ inches of a common side or rear wall sits inside your clear space.

Regulation 29(a), printed page 25.

Avenir professional observation — not a DHA statement

Deduct the wall and the fractions resolve. On a 1 Kanal plot, the 15′-9″ front clear space less the 9 inch front boundary wall leaves exactly 15′-0″ of open ground between the wall and the building face; the 5′-4½″ side and rear clear spaces less 4½ inches of common wall each leave exactly 5′-0″. The same holds for 10 Marla and 2 Kanal. The odd half-inches in the published table exist because the wall thickness is included in the dimension. For 9 Marla and below the table states round figures that already include the wall, so the usable open ground on those plots is less than the headline number. Confirm this reading with Building Control before relying on it in a submission.

What may and may not sit in a clear space

No construction, even temporary, may be carried out in the clear spaces, except:

  • Stair for basement, 2.5 ft wide
  • Underground water tank
  • Drains
  • Septic tank or tanks
  • Sewer line
  • Spiral steel stair at the rear, where a servant quarter is located at the first floor

Clear spaces cannot be covered by constructing pergolas. However, a 2 foot pergola or sunshade may be extended into the clear spaces at ground and first floor. At ground floor a sunken area may be extended into the clear spaces leaving a 2.5 ft wide clear passage, in the case of construction of a basement. A spiral steel stair is allowed in the rear side specified clear space for roof-top access; no platform may be provided with it, and concrete sun shades may not be used as a platform or landing.

Regulation 22(a), Notes 1 to 3, printed page 21. Sunken area also at Regulation 35(b), printed page 28.

Two further restrictions sit elsewhere in the document and are easy to miss. No balcony may be made over clear spaces. And only one temporary shade of 6 ft × 4 ft is allowed in the mandatory rear clear space, for covering a washing machine or similar, subject to safety requirements — particularly fire safety and fire fighting — and after obtaining permission from DHA.

Regulation 27(a)(4) and Regulation 27 Note 2, printed pages 24–25.

Covering an open area or a pergola with fibre glass, steel structure, asbestos cement sheet or other similar material is counted as covered area. A pergola is defined as a structure with a perforated roof of which at least 50% is open to sky. Once you sheet it, it stops being a pergola and starts consuming your covered area allowance.

Regulation 27 Note 1, printed page 25. Definition 68, printed page 10.

Odd-shaped and non-standard plots

Where a plot is irregular in shape, dimension or size, the open area required as clear spaces on each side is to be kept clear in totality, instead of as a uniform space measured from the boundary wall. The permissible area to be covered is built, leaving the rest open. On a non-standard plot, permissible covered area proportionate to the plot size may be covered.

The floor that applies to every plot: the width of clear space on any side, for any size of plot, shall not be less than 3 feet 9 inches.

Regulation 22(b)(1) to (4), printed page 21. Definition 61, printed page 9.

Corner plots

On a corner plot, if the owner intends to keep the frontage on the longer side, the specified front clear space must be left on both the sides. On a 1 Kanal corner plot taken frontage-long, that means 15′-9″ on two sides rather than one — a materially different envelope from the same plot planned the other way round, and a decision that has to be made at concept stage because it changes the entire plan.

Two further corner-plot rules: the gate may not be provided in the chamfered portion of the boundary wall, and a corner plot may have two porches resting on the boundary wall where a non-corner plot of the same size may have one.

Regulation 22(c), printed page 21. Regulation 29(d), printed page 26. Regulation 27(a)(8), printed page 24.

Not sure which figures apply to your plot? Send the size, phase, block and whether it is a corner plot. We will confirm the envelope before you commit to a plan.

Confirm my clear spaces

Covered Area and Floor Limits

  • Basement100% of the allowable covered area, excluding the porch area, for a house without a dead wall. Where a dead wall exists, 5 feet must be left. Only a single storey basement is permitted in a residential area.
  • Ground floorMay cover the plot leaving the specified clear spaces. There is no separate percentage cap on the ground floor of a standard residential plot — the clear space table is the cap.
  • First floorA percentage of the ground floor, set by plot size. See the table below.

Regulation 27(a)(1) and (2), printed page 24. Regulation 35(a), printed page 27.

First floor — the percentage table

Reg 27(a)(3) — permitted first floor covered area
Plot sizePermitted first floor covered area
5 Marla100% of ground floor
7 to 10 Marla82% of ground floor
1 Kanal80% of ground floor
2 Kanal78% of ground floor
3 Kanal78% of ground floor
4 Kanal78% of ground floor

Regulation 27(a)(3), printed page 24.

Why 3 and 4 Kanal appear here

Regulation 4(a) sets the maximum size of a residential plot at 2 Kanal (9,000 sq ft). Three and four Kanal residential plots therefore exist only through amalgamation, which Regulation 8 permits for 1 Kanal and 2 Kanal plots up to a maximum amalgamated size of 4 Kanal. On amalgamated plots a second and separate cap applies: the footprint area of an amalgamated 4 Kanal plot must not exceed 63% of plot area, and a 3 Kanal plot must not exceed 65%. So an amalgamated plot is governed by a footprint percentage of the plot and a first floor percentage of the ground floor at the same time. Constructed houses may not be amalgamated; one house and one open plot can be.

Regulation 4(a), printed page 13. Regulation 8(a)(2) to (4) and 8(b), printed pages 14–15.

What the percentage actually means on your plot

The first floor limit is not a discount. It is an instruction about massing, and the larger the plot the more of the ground floor roof it forces you to leave unbuilt.

Illustration — gross envelope arithmetic
PlotMax ground floor envelope First floor limitGround floor roof left unbuilt
5 Marla, 25′×45′19′-0″ × 37′-0″ = 703 sq ft100% = 703 sq ftNil
10 Marla, 35′×65′24′-3″ × 48′-10½″ = 1,185 sq ft82% = 972 sq ftapprox. 213 sq ft
1 Kanal, 50′×90′39′-3″ × 68′-10½″ = 2,703 sq ft80% = 2,163 sq ftapprox. 540 sq ft
2 Kanal, 100′×90′89′-3″ × 65′-10½″ = 5,879 sq ft78% = 4,586 sq ftapprox. 1,293 sq ft
2 Kanal, 75′×120′64′-3″ × 90′-10½″ = 5,839 sq ft78% = 4,554 sq ftapprox. 1,285 sq ft

Avenir calculation from the plot dimensions at Regulation 4(a), the clear spaces at Regulation 22(a) and the percentages at Regulation 27(a)(3). Figures are gross envelope areas before wall thickness, porch, projections and any sunken area, shown to illustrate the scale of the constraint. They are not DHA-issued figures and are not a substitute for a schedule of areas prepared for your plot. The 75′×120′ buildable depth of 90′-10½″ is confirmed by DHA’s own Annex A sub-division drawing at printed page 44.

Avenir professional observation

On a 2 Kanal plot roughly 1,300 square feet of ground floor roof cannot be built on. That area is not spare — it is a design problem with a deadline, because the byelaws constrain what you can do with it. No balcony may be made over clear spaces. A 2 foot sun or rain shade may not be combined with an open terrace except on the front and road side of a corner plot. So the unbuilt roof has to be resolved as a usable terrace served from inside the first floor, a courtyard void, or a double-height volume — and each of those changes the ground floor plan underneath it. Decide it at concept. Discovering it when the first floor plan is drawn means replanning the ground floor.

Sun shades, projections and railings

A 2 foot wide sun or rain shade and roof projection with a 6 inch drop down is permitted. A sun or rain shade is defined as an outer-side 2 foot wide projection from the building, over a minimum height of 7 feet from plinth level.

The shade may not be combined with an open terrace, except on the front and road side in the case of a corner plot. It may not be used as a balcony, walkway or passage. No construction, parapet or railing is permitted on the shades — with one exception: a railing or parapet up to 36 inches in height may be provided on the front or road-facing side sun shade or roof projection of the ground and first floor. No balcony may be made on clear spaces.

Regulation 27(a)(4), printed page 24. Definition 90, printed page 11.

Avenir professional observation

This is, in our practice, the single most misread clause in the residential section, and it shows up in elevations rather than plans. The default reading is “railings up to 36 inches are allowed on shades”. The clause says the opposite: railings on shades are prohibited, and are then permitted only on the front or road-facing side. An elevation showing a continuous railed projection wrapping the side and rear of the house does not comply, and because it is an elevation issue it survives every plan check until scrutiny.

Working out how much you can actually build? Send your plot size and dimensions and we will return the permitted envelope and first floor area for your plot.

Check my covered area

Maximum Height

39 ft Maximum height of a residential building of any type, from the crown of the road, for all phases.
32 ft Where the building has no mumtee and parapet. In that case a second floor is not permitted.

Regulation 23(a), printed page 22.

Height of building is defined as the vertical measurement from the crown of the front road to the highest part of the roof — not from your plinth, and not from your finished ground level.

Definition 49, printed page 8.

ElementLimitRegulation
Residential building, all phases39 ft maximum from crown of roadReg 23(a), p22
Without mumtee and parapet32 ft; second floor not permittedReg 23(a), p22
Maximum height of ground / first floor18 ftReg 32(b), p26
Ceiling height, living roomsNot less than 9 ft 6 inReg 32(b), p26
Basement ceilingNot less than 9 ft, not more than 14 ftReg 32(c), p26
Basement excavationNot more than 12 ft 0 in with foundation, from crown of road levelReg 32(c), p26
Stair mumtee area, up to 10 Marla175 sq ftReg 33(a)(1), p27
Stair mumtee area, 1 to 4 Kanal300 sq ftReg 33(a)(2), p27
Lift machine room, residentialMaximum 75 sq ft; height 45 ft from crown of road levelReg 33(a), p27
Rest of mumtee other than machine roomRemains 39 ft 0 inReg 33(a), p27
Boundary wall7 ft maximum from crown of adjacent roadReg 29(a), p25
Boundary wall plus electric fence9 ft 6 in total (7 ft + 2 ft 6 in); concertina wire not allowedReg 29(b), pp25–26
Guard postInner size 6 ft × 6 ft, maximum height 8 ft from road levelReg 37(a), p28
Avenir professional observation

The 39 foot cap is almost never broken by the house. It is broken by the overhead water tank. Regulation 15(m) requires the drawings to show the overall height of the building including the overhead water tank, staircase, machine room for lift and parapet walls — so the tank is inside the 39 feet, and it is the one element that is routinely sized and positioned after the section has been drawn. The only element the regulations allow above 39 feet on a residential building is a lift machine room, capped at 75 square feet and 45 feet; the rest of the mumtee stays at 39 feet 0 inches. Set the tank level in the section at concept stage, not when the plumbing is designed.

Two further constraints on the mumtee: where plots are amalgamated, the area of the stair or lift mumtee remains the same as that of the original plot. And the stair mumtee must be designed to cover the stair area only — no living space may be created within it.

Regulation 33 Notes 1 and 2, printed page 27.

Section showing the 39 foot residential height limit measured from road crown in DHA Lahore
The 39 ft envelope measured from road crown, with mumtee, overhead tank and lift machine room. [Replace with Avenir drawing.]

Car Porch Rules

A car porch is defined as a shelter or shed for a car which is permanently open on at least two sides.

Definition 27, printed page 7.

RuleRequirementRegulation
Column sizeNot less than 9 inches × 18 inches, or 12 inches diameterReg 27(a)(5), p24
Void above boundary wallOptional. May be blocked, or provided with grill, cemented jali or louversReg 27(a)(6), p24
Load bearingThe roof of the car porch shall rest on columns or beam and not on the boundary wallReg 27(a)(6), p24
Porch columns and the common wallThe common boundary wall shall not be used for construction of car porch columns. Columns shall be constructed adjacent to the boundary wall; the roof can be extended up to the plot limitReg 29(g), p26
Height where resting on boundary wallNot less than 9 feet and not more than the roof level of the ground floorReg 27(a)(7), p24
Number on boundary wall — 2 KanalTwoReg 27(a)(8)(a), p24
Number on boundary wall — 1 KanalOne. A corner plot may have twoReg 27(a)(8)(b), p24
Number on boundary wall — up to 10 MarlaOne. A corner plot may have twoReg 27(a)(8)(c), p24
Maximum width9 feetReg 27(a)(9), p24
Minimum depthNot less than 12 feet, excluding the 2 foot projectionReg 27(a)(9), p24
Maximum depthNot exceeding 18 feet, excluding the 2 foot projection, where the clear space is covered for construction of the car porchReg 27(a)(9), p24
Temporary or removable extensionsThe far end of the cantilever extension must be at least 2 feet away from the front property line. Extensions are permitted only in front of the existing car porchReg 27(a)(10), p25
Plot abutting two parallel roadsAn additional porch may be constructed on the rear side, leaving the specified clear spaceReg 27(a)(11), p25
Confirm with Building Control before designing to it

Regulation 27(a)(6) states that the porch roof shall rest on columns or beam and not on the boundary wall. Regulations 27(a)(7) and 27(a)(8) then set a height limit and a per-plot-size count for porches “resting on boundary wall”. Regulation 29(g) adds that the common boundary wall may not carry porch columns, that columns must sit adjacent to it, and that the porch roof may extend to the plot limit. Read together, the practical position appears to be that the porch is structurally independent of the wall while spanning over it, but the clauses are not worded consistently. Confirm the current position with the DHA Building Control Directorate for your specific plot before finalising the porch structure.

Checking a constraint mid-design? Send your drawings and we will check them against the current byelaws before they go to Building Control.

Get my drawings checked

Basement, Plinth, Boundary Wall, Rooms, Mumtee, Tanks and Pool

Seven sets of residential limits, grouped so you can open the one you need. Every panel is expandable and all content is on the page.

Basement
  • Single storey basement is permitted in a residential area.
  • Where a basement is built, the plinth of the ground floor shall be 3 feet 6 inches from the crown of the front road, up to 10 Marlas. The plinth height can be relaxed up to the normal plinth level where a sunken area is provided.
  • A sunken area can be extended into the clear space leaving at least a 2.5 foot wide clear passage.
  • Basement ceiling height not less than 9 feet and not more than 14 feet. Excavation not more than 12 feet 0 inches with foundation, measured from crown of road level.
  • Coverage: 100% of allowable covered area excluding porch, for a house without a dead wall; leave 5 feet where a dead wall exists.

Regulation 35(a) and (b), printed pages 27–28. Regulation 32(c), printed page 26. Regulation 27(a)(1), printed page 24.

Avenir professional observation

The basement decision is not a basement decision. It sets the ground floor plinth at 3′-6″ on plots up to 10 Marla, which sets the entrance step count and the driveway ramp — and the top of the ramp and the clear spaces may not be more than 12 inches higher than the crown of the front road. Change your mind about a basement after the ground floor plan is fixed and you are not adding a floor below, you are replanning the approach, the porch level and the entry sequence. Take the decision before the ground floor plan is finalised, not at excavation.

Plinth level

The plinth level of the building shall not be less than 1 foot 6 inches from the crown of the adjoining road and a maximum of 3 feet 6 inches. It can be increased up to 5 feet 6 inches on one Kanal and above plots. The top of the ramp and clear spaces shall not be more than 12 inches higher than the crown of the front road, and the ramp shall be made as per the approved plan. Plinth is defined as the finished floor level of the building.

Regulation 28(a) and (b), printed page 25. Definition 71, printed page 10.

Boundary wall
  • 9 inches thick, using 4½ inches of the adjoining plots, provided the layout has been approved by the Authority. No space from the Right of Way of the road or street may be used.
  • Boundary walls are considered common boundary walls and all neighbours have rights to use them on their respective sides and top.
  • Maximum height 7 feet from the crown of the adjacent road.
  • A maximum 2 foot 6 inch high electric wire fence may be erected on the common boundary wall after submitting an undertaking regarding functionality and neighbour safety. Total height of wall plus fence not more than 9 feet 6 inches. Concertina wire is not allowed.
  • Before starting the main building, boundary walls shall be got checked at ground level.
  • The gate of a house on a corner plot may not be provided in the chamfered portion of the boundary wall.
  • Rockery or hard landscaping outside the boundary wall is strictly prohibited. A 2 foot wide flowerbed of small plants parallel to the wall, of bricks or similar material, maximum height 6 inches, is permitted.
  • Coping towards the road side may protrude up to 4 inches.
  • In the case of blood relation ownership, a door may be installed or the common boundary wall removed between two houses. On transfer, excluding Hibba, the owner must close the door or reconstruct the wall before transfer.

Regulation 29(a) to (h), printed pages 25–26.

Room sizes, heights and inter-floor spaces
  • Minimum size of a living room: not less than 100 square feet, with a minimum dimension not less than 9 feet. All rooms shall be well lit and well ventilated.
  • Height of ceiling of living rooms: not less than 9 feet 6 inches. Maximum height of ground or first floor: 18 feet.
  • Height of a room is measured between the finished floor level and the underside of the ceiling. Head room is measured to the underside of the lowest obstruction, whichever is lower.

Inter-floor spaces. An inter-floor having not more than 40% of the area of a liveable space, at ground or first floor, is allowed for residential units, subject to:

  • One inter-floor space for plot sizes 9 Marla to 1 Kanal. Two for 2 Kanal and above.
  • Minimum clear height 8 feet, in compliance with the total permissible height of 18 feet.
  • Closure with brick masonry, glass partition or similar material is not allowed. Only a 3 foot 0 inch high railing is allowed on the upper level.
  • No water supply or sewerage services are permitted, and it cannot be used as a bath, kitchen, store, dressing room or walk-in-closet.

Regulation 32(a) to (d), printed pages 26–27. Definitions 48 and 50, printed page 8.

Staircase, mumtee and lift machine room

For residential buildings the maximum area of the machine room for a lift is 75 square feet and its height shall be 45 feet from crown of road level. The height of the rest of the mumtee, other than the machine room, remains 39 feet 0 inches. The area of the stair mumtee is 175 square feet up to 10 Marlas and 300 square feet for 1 to 4 Kanals. Where plots are amalgamated, the mumtee area remains the same as that of the original plot. The stair mumtee must be designed to cover the stair area only and no living space may be created.

Separately, the thickness of all walls enclosing a staircase shall not be less than 9 inches in brick masonry, and 6 inches in RCC.

Regulation 33(a) and Notes 1 and 2, printed page 27. Regulation 41(c), printed page 32.

Water tanks and water supply

The person shall construct underground and overhead water tanks in the house and make the necessary arrangements for pumping water from the underground tank to the overhead tank. The Authority is responsible for ensuring that water reaches the underground water tank.

No person is permitted to bore a well, tube well, water pump or hand pump for an alternative supply of water, or to install a motor or pump directly on the water supply line in any way. A person who does so is liable to fine, penalty or both, in addition to detachment and confiscation of the motor or pump. The Authority may allow boring of a shallow pump for construction purposes only, and on completion the bore must be destroyed.

Regulation 36, printed page 28. Regulation 11(f), (g) and (h), printed pages 15–16.

Swimming pool, guard post, rockery and surface water

Swimming pool. Construction is not permitted in a residential building having an area less than one Kanal, nor on the roof top. To ensure privacy, a 10 foot high wall or any other arrangement as directed by the Authority must be provided. Separate charges are levied for a house having a swimming pool.

Guard post. Inner size 6 feet × 6 feet with a maximum height of 8 feet from the road level adjacent to the main gate, towards the lawn. On production of an authorisation letter from the Federal or Provincial Home Secretary, a guard post may be placed for the prescribed duration adjacent to the boundary wall near the main gate, not utilising more than 8 feet × 12 feet of the berm area. No permanent or temporary guard post, including tents or cabins, may be provided outside the boundary wall.

Rockery and water features. A rockery or water feature up to the height of the boundary wall may be constructed with the front boundary wall. Along a common boundary wall a minimum 6 inch gap must be provided. In clear spaces, leave a clear passage of 2.5 feet between the building and the feature.

Surface water. A water channel of 3 inch × 3 inch size shall be constructed outside the house as approved in the drawing, connected to the internal septic tank through a “P” trap.

Regulation 34, printed page 27. Regulation 11(i), printed page 16. Regulation 37, printed page 28. Regulation 46(g), printed page 33. Regulation 31, printed page 26. Regulation 30, printed page 26.

Fire Safety Requirements for Houses

Fire protection drawings are one of the five sets DHA scrutinises. Annex-C to the regulations sets the mandatory provisions for houses by plot size. This is the section of the byelaws least covered elsewhere and the one that most often collides with a construction programme, because the wiring has to be cast into the structure.

Regulation 16(a)(3), printed page 19. Regulation 41(e), printed page 32. Annex-C, printed page 46.

Annex-C — fire safety requirements for houses
Measure 5 Marla10 Marla 1 Kanal2 Kanal
Smoke / heat detectors — ground floor 0509 1737
Smoke / heat detectors — first floor 0607 1429
Smoke / heat detectors — basement 01 per 150 sq ft01 per 150 sq ft 01 per 150 sq ft01 per 150 sq ft
Detectors — compartments At least 01 in each compartment, at least 01 per 150 sq ft At least 01 in each compartment, at least 01 per 150 sq ft At least 01 in each compartment, at least 01 per 150 sq ft At least 01 in each compartment, at least 01 per 150 sq ft
Manual call points 01 per floor01 per floor 01 per floor, 01 in servant quarter 02 per floor, 01 in each servant quarter
Fire alarm sounders 01 per floor in living area, 01 in garage / gallery 01 per floor in living area, 02 in garage / gallery (front / rear) 01 per floor, 01 in servant quarter, 02 in garage / gallery (front / rear) 01 per floor, 01 in each servant quarter, 02 in garage / gallery (front / rear)
Emergency lights 01 per floor01 per floor 02 per floor, 01 in servant quarter 02 per floor, 01 in each servant quarter
Fire extinguishers 02 DCP (6 kg) on each floor, 01 CO₂ (6 kg) in each house 02 DCP (6 kg) on each floor, 01 CO₂ (6 kg) in each house 02 DCP on each floor, 01 CO₂ in each house, 01 DCP in servant quarter, 01 CO₂ in servant quarter 03 DCP on each floor, 01 CO₂ in each house, 01 DCP in each servant quarter, 01 CO₂ in servant quarters
Fire blankets 02 in each house02 in each house 02 in each house, 01 in servant quarter 02 in each house, 01 in each servant quarter
Emergency first-aid box 01 in each house01 in each house 01 in each house01 in each house
Fire alarm control panel box Close to main entry / exit at ground floor Close to main entry / exit at ground floor Close to main entry / exit at ground floor Close to main entry / exit at ground floor
Electrical DB installation Close to main entry / exit at ground floor Close to main entry / exit at ground floor Close to main entry / exit at ground floor Close to main entry / exit at ground floor

Annex-C, “Fire Safety Requirements for Houses”, printed page 46. The published table also covers 8 Marla, where the ground and first floor detector counts are 08 and 06. Additional requirements applying to all plot sizes: a wet chemical fire extinguisher, at least one per kitchen (recommended); and heat detectors at least 01 per kitchen in kitchens, pantry or cooking area, plus 01 per 150 sq ft for additional space.

Two requirements printed beneath the Annex-C table apply to every plot size and are not optional:

  • Installation of fire protection equipment should be done using fire resistant cable.
  • No wireless smoke or heat detectors should be installed. Smoke and heat detectors must all be connected to the fire alarm control panel along with the fire alarm sounders and manual call points.

Electrical wiring for the fire protection system must be run in separate conduits.

Avenir professional observation

Because wireless devices are prohibited and everything must be hard-wired back to a panel in fire-resistant cable in separate conduits, the fire system is a grey structure item, not a finishing item. Those conduits are cast into slabs and chased into walls while the structure is going up. Treat fire protection as something to specify after plaster and the choice narrows to surface-mounted conduit in a premium house, or chasing finished walls. On a 2 Kanal house the table requires 37 detectors at ground floor and 29 at first floor — that is a distribution problem for the electrical layout, and it needs to be coordinated with the reflected ceiling plan before the slab is poured.

Fire protection drawing layout submitted with a DHA Lahore house map
Fire protection layout submitted as one of the five scrutinised drawing sets. [Replace with Avenir drawing.]

Privacy, Rooftop Use, CCTV, Solar and Generator

These sit in Part IV of the regulations and are the rules owners most often ask about late in design, when changes are expensive.

Privacy

Reg 57 · p38

  • Construction and erection shall be carried out on the norms of privacy of the neighbours.
  • The purdah wall of the servant terrace shall be kept 7 feet from the floor.
  • The sill level of a servant’s quarter window shall not be less than 7 feet.
  • Servant entry in front of the spiral stair at first floor shall be maximum 3 feet.

Regulation 57(a) to (d), printed page 38.

Green rooftop

Reg 65 · p41

  • Plant height should not be more than 4 feet 0 inches.
  • Plantation along the parapet wall, to create an offset ensuring the privacy of neighbours. In the case of a common wall, a 1 foot distance shall be maintained.
  • No sheds or pergolas — fibre, glass, steel or wooden — are allowed to be constructed.
  • No louvers or railing will be fixed on the 3 foot parapet wall.
  • The member will furnish an undertaking that neighbour privacy will not be compromised and the rooftop will not become a nuisance.

Regulation 65(a) to (e), printed page 41.

Misuse of rooftop

Reg 61 · p40

In the area of the Authority adjacent to the Civil Aviation Airport, the following are strictly prohibited on rooftops to avoid bird hazard and reduce the risk of bird strike: keeping birds or pet animals on the rooftop; throwing or spreading food articles, foodstuff, meat and other eatable articles; and roosting and breeding facilities.

Regulation 61, printed page 40.

CCTV cameras

Reg 66 · p41

  • All residential buildings must install at least two CCTV cameras at both ends of the front boundary wall.
  • Corner plots must install an additional camera covering the side view and street junction.
  • The system must be operational 24/7 and regularly maintained.
  • A minimum of 10 days of footage must be stored at all times, and provided to DHA Security or a law enforcement agency on request.
  • Failure to provide footage when required may result in fines. The Authority may inspect and enforce compliance.

Cameras at both ends of the front boundary wall need power and data at those positions. That is a conduit run in the boundary wall and along the front elevation, and it belongs on the MEP drawing rather than on a security contractor’s quotation after handover.

Regulation 66(a) to (d), printed page 41.

Solar system installation

Reg 67 · pp42–43

Solar systems shall only be procured and installed by vendors approved or authorised by the Private Power Infrastructure Board (PPIB), including work eligibility in Punjab. A complete proposal must be submitted to DHA for scrutiny and approval before installation.

  • 1 Kanal and above: panel upper edge maximum 10 ft from roof; lower edge maximum 5 ft from roof.
  • 5 to 10 Marla: upper edge maximum 12 ft (strictly) from roof; lower edge varying according to available space. Inverters and panels must be of a Tier 1 system.
  • Mumtee, machine room and overhead water tank areas shall not be used without prior permission. Where permitted: upper edge maximum 1 ft 6 in from mumtee roof, lower edge maximum 2 inches.
  • Permanent structures integrated into the grey structure are not permitted. The structure shall be grounded with the roof using stainless steel anchors only, with roof waterproofing ensured. Concrete footings shall strengthen structural steel columns.
  • AC/DC earthing and a lightning arrester are mandatory for all installations.
  • Documents: LESCO NOC or electricity bill showing DG load; valid PPIB licence copy; original structure stability certificate against wind velocity (100 km/h standard, 125–140 km/h elevated or customised); original commissioning certificate.

Regulation 67(a) to (d), printed pages 42–43.

Generator (residential)

Reg 58 · p39

A generator shall not be used as a prime source of electric supply. It may be used as standby, subject to:

  • Petrol or diesel driven with a sound proof canopy. Gas driven requires prior written permission from the Gas Regulatory Authority.
  • Noise beyond the boundary limit not more than 95 decibel.
  • Placement: basement with proper ventilation; rooftop on the front side; or front lawn 5 ft away from the common boundary wall. Not in rear and side clear spaces at ground floor, or on terraces at first floor.
  • Stability certificate from a qualified structural engineer for the soundness of the roof slab against weight and vibration.
  • An affidavit to compensate damage to adjoining property and to remove the generator when directed.
  • Rooftop access through an internal stair, or a rear spiral stair, is compulsory to install on the rooftop.
  • Maximum capacity 25 KVA for a residential building.

Regulation 58(a), printed page 39.

Avenir professional observation — solar

Two clauses pull against each other and both have to be satisfied. Permanent structures integrated into the grey structure are not permitted for the solar mounting, yet concrete footings must be designed and constructed to strengthen the structural steel columns, and the structure must be anchored to the roof with stainless steel anchors only. In practice that means the roof slab has to be designed for a solar load and detailed for anchor positions and waterproofing at the design stage, while the mounting structure itself stays demountable. A slab designed without that load, later drilled for anchors, is a waterproofing failure waiting to happen on a roof you have already finished.

Violations and Enforcement

Stated as the regulations state it, without embellishment.

Construction without approval

No construction, addition, alteration, renovation or demolition is allowed without prior approval of the Authority. Construction without approval of the building plan is not permitted and shall be demolished at the risk and cost of the owner.

Regulation 13(c), printed page 16. Regulation 21, printed page 21.

Changes after approval

A revised drawing is required for approval by the Authority before execution of any addition or alteration in the structure of the building. Renovation not affecting the structure may be carried out after obtaining approval from the Authority.

Regulation 20, printed page 21. Definition 82, printed page 11.

What counts as a construction violation

Regulation 46 states that construction violations shall include, but are not limited to:

  • Tampering with the sewer manhole for drainage of surface water.
  • Ramp slope not finishing within 5 feet from the boundary wall; driveway slope not conforming to the road slope towards the house.
  • Installing water points or taps outside the boundary wall of a residential building, or outside a commercial building.
  • Permanent or temporary fence, rockery, hedge or other such structures outside the boundary wall.
  • Earth filling outside the boundary wall other than 2 inches below the adjoining road edge, and slope of the berm area towards the building.
  • Permanent or temporary guard post, including tents or cabins, outside the boundary wall.
  • Damaging the road by mixing concrete or cutting and bending steel bars on the road, or placing a concrete mixer on the road berm.
  • Cutting the road surface without written approval, causing damage to the road, or erecting speed breakers or any other obstruction on the road.
  • Providing permanent brick soling, pavers or concreting along the metal road in the berm area.
  • Installation of a generator in violation of the rules and regulations of the Authority.
  • Any other violation which is declared as such by the Authority as per its prevailing rules and regulations.

Regulation 46(a) to (l), printed pages 32–33. The regulations also note that since the area outside the boundary wall is liable to be dug by the Authority for connections or maintenance without intimation, a person should not construct costly ramps.

How enforcement works

If on inspection the building work is found to be in contravention of any of the regulations, the Authority gives due notice with the object of bringing the works into conformity with the approved plan, or of stopping the work until the approval of an amended or revised plan. In the event of non-compliance the work shall not proceed further, and the Authority may order the demolition of that much of the construction as contravenes the regulations, at the cost of the person. The Authority reserves the right to disconnect or refuse services and to impose a fine; water supply and sewerage services are restored on payment of the fine, if any, and restoration charges.

Where the Authority finds a violation it serves a notice in writing indicating the nature of the violation. Where violations are not removed or regularised within the stipulated period, the Authority may disconnect the services of the member. Services are restored after removal or regularisation and payment of restoration charges.

Regulation 19(b) and (c), printed page 20. Regulation 47(a) to (c), printed page 33.

Right of appeal

If the person is dissatisfied with a notice issued under the regulations, they can file an appeal before the Administrator within 15 days to reconsider the case, provided that work is suspended on filing of the said appeal and until the decision of such appeal. The Authority decides the appeal after hearing the applicant within such period as consented or agreed upon. If the appeal is rejected, the appellant is bound to rectify the violation within the period specified in the decision.

Regulation 19(d) and (e), printed page 20.

Received a violation notice? There is a 15 day window to file an appeal. Send the notice and your plot details and we will tell you what your options are.

Discuss my notice

Powers of the Executive Board

Where building works are commenced or carried out contrary to the provisions of the regulations or the approved building plan, the Authority may by written show cause notice require the person to stop all works forthwith. If the person fails to show sufficient cause, the Authority may require the person to demolish the whole building or part thereof; and in case of failure to demolish, the Authority shall demolish such works at the risk and cost of the person. In case of non-compliance, registration may be cancelled and the premises may be taken over by the Authority.

Regulation 69(a) and (b), printed page 43.

Cancellation of permission

If at any time after permission has been granted the Authority is satisfied that it was granted in consequence of any defective title, material misrepresentation, or a fraudulent statement contained in the application, plan, elevations, sections or specifications, the permission may be cancelled and any work done thereunder shall be deemed to have been done without the permission of the Authority.

Regulation 62(a), printed page 40.

Excavation and adjacent buildings

  • No excavation, dewatering, earthwork or demolition likely to affect the stability of an adjacent building is allowed unless adequate steps are taken before and during the work to prevent total or partial collapse or damage.
  • Demolition is not permitted without prior approval of the Authority, and a defaulter may be violation charged. Demolition shall only be carried out under the supervision of a professional engineer, with prior approval.
  • Owners must obtain prior permission from the DHA Building Control Directorate before using an excavator. The application is made with an undertaking on Rs 100 stamp paper, together with a deposit of Rs 100,000 as refundable security via challan. Refund is subject to site inspection and clearance; deductions apply for damages.
  • Any excavation posing a threat to public safety must be appropriately marked and protective works erected. Failure makes the person liable to be penalised, including making good any losses.

Regulation 42(a) and (b), printed page 32. Regulation 44, printed page 32. Regulation 68(a) to (c), printed page 43. Regulation 43(c), printed page 32.

Who is responsible for supervision

“Construction supervision and quality assurance shall be the sole responsibility of the member and his appointed architects / engineers.”
Regulation 45, printed page 32.

Read that clause alongside two others. The note to Regulation 18 states that permission granted after inspection at any stage does not relieve the registered person of the responsibility of keeping the construction free of all violations. Regulation 16(f) states that any oversight in the scrutiny of documents at the time of approval does not entitle the person to violate the regulations or claim damages.

Avenir professional observation

Three separate clauses place the risk on the owner. DHA’s stage verifications are compliance checkpoints, not a quality service, and an approval stamp is not a defence. This is why an unsupervised contractor arrangement in DHA Lahore is a regulatory exposure rather than only a quality risk: if a violation is built, the notice, the rectification cost and the demolition liability sit with the owner, not with the contractor who built it. The regulations name the architect and engineer appointed by the member as the parties who carry supervision with the owner — which is an argument for appointing them, in writing, with a defined supervision scope.

Common Reasons a DHA Lahore Submission Is Returned

Avenir professional observation — not a quotation from the byelaws

No frequency, percentage or ranking is stated because we do not hold published data on DHA’s returns and will not invent it. Each item names the regulation the observation relates to, so the underlying requirement is checkable even though the observation is ours. DHA decides every submission on its own merits.

In our experience the observations that come back on returned submissions cluster around documentation and arithmetic rather than around design ambition. The recurring ones:

  1. The architect is registered with PCATP but not with DHA

    The regulations define a registered architect as registered with PCATP as well as registered with the Authority. A drawing signed by an architect who is not on DHA’s register is not a valid submission, and the point is usually discovered at the counter.

    Regulation 15 opening paragraph, p18; Definition 76, p10.
  2. The geotechnical report is missing, or older than a year

    Regulation 14(p) requires an original soil testing or geotechnical report with a validity of one year. Owners who commissioned a report early in the plot-purchase process sometimes find it has expired by the time the drawings are ready.

    Regulation 14(p), p17.
  3. Overall height shown without the overhead tank, mumtee, machine room or parapet

    The section has to show the overall height including all of these, measured from the crown of the front road. A section drawn to the roof slab is incomplete and, once the tank is added, sometimes non-compliant.

    Regulation 15(m), p18; Regulation 23(a), p22.
  4. The schedule of areas does not reconcile with the plans

    Regulation 15(c) requires a schedule of open, covered and permissible areas. Where the first floor percentage has been calculated on a different ground floor figure from the one the plan actually shows — usually because a porch, projection or sunken area has been treated inconsistently — the arithmetic fails on inspection even though the design would have complied.

    Regulation 15(c), p18; Regulation 27(a)(3), p24.
  5. Structures shown in the clear spaces beyond the permitted list

    Steps, planters, covered side passages, storage, pergolas covering the clear space, or a platform at the spiral stair. The permitted list is short and closed: basement stair 2.5 ft wide, underground water tank, drains, septic tanks, sewer line, rear spiral steel stair where the servant quarter is at first floor, plus the 2 ft pergola or sunshade extension and the ground floor sunken area with a 2.5 ft passage.

    Regulation 22(a) Notes 1 to 3, p21.
  6. Railings shown on sun shades other than on the front or road-facing side

    An elevation issue rather than a plan issue, which is why it survives internal checking.

    Regulation 27(a)(4), p24.
  7. Porch dimensions outside the permitted range, or a second porch on a non-corner plot

    Maximum width 9 feet; depth not less than 12 feet and not more than 18 feet, both excluding the 2 foot projection; one porch resting on the boundary wall on a non-corner 1 Kanal or 10 Marla plot.

    Regulation 27(a)(8) and (9), p24.
  8. Fire protection drawings absent, or not matching Annex-C for the plot size

    Fire protection is one of the five scrutinised sets. A submission carrying architectural, structural and MEP drawings but no fire protection set is incomplete.

    Regulation 16(a)(3), p19; Annex-C, p46.
  9. Drawing scales not at the specified ratios

    Plan and elevation at 1 inch = 8 ft; cross-sections and longitudinal sections at 1 inch = 4 ft.

    Regulation 15(q) and (r), p18.
  10. Cross-section of the boundary wall towards the road not shown

    A small omission with the same consequence as a large one.

    Regulation 15(n), p18.
  11. Certificates missing or issued by the wrong party

    The architect’s certificate confirming that all components of the building were designed by them, and the structural stability certificate from a registered structural engineer, are both required. So are the separate electrical and mechanical engineer’s certificates listed in Regulation 14.

    Regulation 15(s) and (t), p18; Regulation 14(e) to (h), p17.
  12. Basement extending into the clear space, or the dead-wall allowance not left

    A basement is 100% of the allowable covered area excluding porch for a house without a dead wall, and 5 feet must be left where a dead wall exists. The sunken area is the element permitted to extend into the clear space, leaving a 2.5 foot passage — not the basement itself.

    Regulation 27(a)(1), p24; Regulation 35(b), p28.
  13. Sub-division and amalgamation cases submitted without the Annex geometry

    Division of a duplex house other than corner follows the sketch at Annex-A; sub-division of corner plots follows Annex-B. Sub-division of a duplex house is only allowed when both portions have been constructed at minimum up to plinth level, and the clear spaces of one Kanal apply to the sub-divided units of a two Kanal plot.

    Regulation 7(a)(6), 7(b)(2), 7(c) and 7(d), p14; Annex-A and Annex-B, pp44–45.

Rather find these before DHA does? Send your drawings and we will check them against the current byelaws before they go to Building Control. A resubmission restarts the 21 working day clock; a pre-submission check does not.

Get my drawings checked

What You Can Do Yourself, and What Requires a Registered Professional

Stated factually. Nothing here is intended to discourage an owner from doing what they can do.

You can do this yourself
  • Obtain the site plan in the current owner’s name from the Building Control DirectorateReg 14(k), p17
  • Obtain and pay the drawing scrutiny challan from the Front DeskReg 14(m), p17
  • Execute the irrevocable general undertaking on Rs 300 stamp paperReg 14(o), p17
  • Commission the soil testing / geotechnical report — you appoint the laboratory; the report must be original and valid for one yearReg 14(p), p17
  • Apply for physical demarcation of the plot after receipt of the approved drawings, on the prescribed formReg 6, p14
This requires a registered professional
  • Prepare and sign the building plans — a registered architect: PCATP registered and registered with the Authority. Not open to the owner or an unregistered draughtsmanReg 15 opening, p18; Definition 76, p10
  • Certify that all components of the building were designed by them — the registered architectReg 15(s), p18
  • Issue the structural stability certificate — a registered structural engineer, PEC registered. For commercial multi-storey, a PEC-registered consulting engineer (M.Sc Structure) with minimum 5 years’ experienceReg 15(t), p18; Definition 36, p7
  • Issue electrical and mechanical engineer’s certificates — the respective engineersReg 14(e) and (f), p17
  • Produce structural design calculations on demand — the applicant, through the structural engineerReg 15(u), p19
  • Supervise construction and assure quality — the member and their appointed architects / engineers, as sole responsibilityReg 45, p32
  • Supervise demolition work — a professional engineer, with prior approval of the AuthorityReg 44, p32
Two things anyone can do on your behalf

Collect approved documents — the applicant in person, or through attorney (Reg 16(e), p19). Submit applications, pay charges and undertake construction — a person authorised under a special power of attorney issued by the Authority (Reg 63, p40).

Overseas Owners: Submitting Without Travelling

The mechanism is in the regulations, not in a service brochure. A registered person may execute a special power of attorney issued by the Authority, in the manner specified by the Authority, authorising a person to submit applications, receive or pay any charges or penalty, and undertake construction on his or her behalf. Separately, after approval the applicant may collect the documents in person or through attorney.

Regulation 63, printed page 40. Regulation 16(e), printed page 19.

Two consequences worth planning around. First, the special power of attorney is issued by the Authority in the manner it specifies, so its execution and attestation need to be arranged in advance rather than in the week the drawings are ready. Second, several documents in the Regulation 14 list are physical originals — tracing cloth prints, an original paid challan, an original geotechnical report, an undertaking on stamp paper, a CD — which means the person holding the attorney has to be physically present at the Building Control Branch. The parts of the process that can be handled remotely are design approval, drawing review and decision-making. The parts that cannot be are counter submission and collection.

How Avenir handles a DHA Lahore submission

Stated as scope, not as a promise of outcome. DHA decides every submission. Avenir’s role is to submit a compliant and complete drawing set and to correct anything the Authority raises.

  • Compliance check at concept stage, before the plan is developed: clear spaces for your plot size and shape, corner-plot frontage decision, permitted ground floor envelope, first floor percentage, basement feasibility against the plinth and ramp consequences, and the height envelope including the overhead tank position.
  • Architectural drawings prepared and signed by a registered architect, with the architect’s certificate under Regulation 15(s).
  • Structural drawings and the structural stability certificate issued by a registered structural engineer under Regulation 15(t).
  • MEP drawings including water supply and sewerage layouts, underground and overhead tank details, septic tank cross-sections, sump, collection chamber and kitchen grease trap, per Regulation 15(f), (h) and (j).
  • Fire protection drawings prepared against the Annex-C provision for your plot size.
  • 3D views with architect’s seal and the AutoCAD soft copy, per Regulation 14(n) and (q).
  • Schedule of open, covered and permissible areas reconciled against the plans, per Regulation 15(c).
  • Coordination of the Regulation 14 document set, and flagging of the items only you can obtain — site plan, CNIC copy, allotment or transfer letter, challan, stamp paper undertaking and geotechnical report.
  • Response to any observations returned by the Authority, and resubmission.
  • Attendance at the five verification stages under Regulation 18, for projects Avenir is constructing or supervising.
  • Completion certificate application support, including the two ammonia copies and the elevation photographs required under Regulation 48(c).
Pre-publication note — remove before going live

[Confirm this scope list against Avenir’s actual standard architecture and Design + Build scope. Any item Avenir does not provide as standard must be removed or marked as an additional service. Verification Register item 58.]

For how remote coordination, approvals and progress reporting work in practice, see our page for overseas Pakistanis building in Pakistan. This page does not repeat that material.

What Avenir does not claim

  • No guaranteed approval. The Authority may reject plans or suggest modifications even where a design does not contravene the regulations, under Regulation 16(c).
  • No guaranteed timeline. The 21 working day scrutiny period is DHA’s, not ours, and it restarts on resubmission.
  • No influence with DHA. Our contribution is a complete and compliant set, submitted correctly the first time.

Building from the UK, US, Canada or the Gulf? Send your plot details and we will explain how submission and approval can be handled through attorney without you travelling.

Discuss remote submission

Frequently Asked Questions

Answer-first, each with the regulation it comes from.

How long does DHA Lahore take to approve a house map?

The Authority scrutinises the drawings and documents within 21 working days, for all residential and commercial buildings. That period covers the building plans, structural drawings, fire protection drawings, MEP drawings and 3D views. It is a scrutiny period, not a guaranteed approval date — the outcome may be approval, rejection or a request for modification.

Regulation 16(a), printed page 19.
What happens if DHA rejects or returns my house map?

The Authority returns the drawings and documents with reasons given in writing, together with guidelines for resubmission. You may resubmit after making the necessary modifications, corrections and rectification of the observations. On resubmission the application is deemed to be a fresh application and a further period of 21 working days commences from the date of resubmission.

Regulation 16(b) and (d), printed page 19.
How long is a DHA approved drawing valid?

Two years from the date of its approval. On the lapse of that two year period you are under an obligation to obtain fresh approval. Separately, a site once excavated must not be kept open and idle beyond the validity period of the building plan — if it is, the Authority will not revalidate the plan.

Regulation 17(c), printed page 19; Regulation 43(a), printed page 32.
By when must I start and finish construction in DHA Lahore?

You must commence construction within 3 years from the date the area was opened for possession or construction by the Authority, failing which a non-construction penalty is payable as prescribed. You must complete the building within 2 years reckoned from the date of approval of the drawing.

Regulation 17(a) and (b), printed page 19.
What are the setbacks for a 1 Kanal plot in DHA Lahore?

For a 1 Kanal plot the minimum clear spaces, including boundary walls, are 15 feet 9 inches at the front, 5 feet 4½ inches at the rear and 5 feet 4½ inches on each side. On a corner plot where the owner keeps the frontage on the longer side, the specified front clear space must be left on both sides.

Regulation 22(a) and (c), printed page 21.
How much of the first floor can I build in DHA Lahore?

The permitted first floor covered area is a percentage of the ground floor: 100% on 5 Marla, 82% on 7 to 10 Marla, 80% on 1 Kanal, and 78% on 2, 3 and 4 Kanal. Three and four Kanal plots arise only through amalgamation, where a separate footprint cap of 65% and 63% of plot area also applies.

Regulation 27(a)(3), printed page 24; Regulation 8(a)(3) and (4), printed page 15.
What is the maximum height of a house in DHA Lahore?

39 feet from the crown of the road, for residential buildings of any type, in all phases. A residential building without mumtee and parapet is limited to 32 feet, and in that case a second floor is not permitted. Height is measured from the crown of the front road to the highest part of the roof, and the drawings must show the overall height including the overhead water tank, staircase, lift machine room and parapet walls.

Regulation 23(a), printed page 22; Definition 49, printed page 8; Regulation 15(m), printed page 18.
Is a basement allowed, and on what size of plot?

A single storey basement is permitted in the residential area. It may cover 100% of the allowable covered area excluding the porch area for a house without a dead wall, leaving 5 feet where a dead wall exists. Where a basement is built the plinth of the ground floor shall be 3 feet 6 inches from the crown of the front road up to 10 Marlas, relaxable to normal plinth level where a sunken area is provided. Basement ceiling height must be not less than 9 feet and not more than 14 feet.

Regulation 35(a), printed page 27; Regulation 27(a)(1), printed page 24; Regulation 32(c), printed page 26.
Who is allowed to sign house drawings submitted to DHA Lahore?

The building plans must be signed by a registered architect, which the regulations define as an architect registered with the Pakistan Council of Architects & Town Planners and also registered with the Authority. The architect must additionally certify that all components of the building have been designed by them. The structural stability certificate for a residential building must come from a registered structural engineer.

Regulation 15 opening paragraph and (s) and (t), printed page 18; Definition 76, printed page 10.
Can an overseas owner submit a DHA Lahore map through an attorney?

Yes. A registered person may execute a special power of attorney issued by the Authority, in the manner specified by the Authority, authorising a person to submit applications, receive or pay charges or penalty, and undertake construction on their behalf. Approved documents may also be collected in person or through attorney.

Regulation 63, printed page 40; Regulation 16(e), printed page 19.
What is a DHA completion certificate and when do I need it?

It is the certificate issued by the competent Authority on completion of construction as per the approved plan. You must contact the Authority for sewer and water connections before occupying the building, and occupation without those connections is liable to fine. The certificate is normally issued within 20 days if no violation is observed and the construction is found to be in accordance with the approved drawing, and the date of sewer opening is treated as the date of completion. You are bound to obtain it within 3 years of approval of the drawing, failing which a fine is levied monthly.

Regulation 48, printed page 34; Definition 28, printed page 7.
Do I need a revised drawing if I change something after approval?

Yes, where the change affects the structure. A revised drawing is required for approval by the Authority before execution of any addition or alteration in the structure of the building. Renovation that does not affect the structure may be carried out after obtaining approval from the Authority.

Regulation 20, printed page 21.
Do I need a soil test for DHA map approval?

Yes. An original soil testing or geotechnical report must accompany the application, and the validity of the report is one year. Because it is required at submission rather than at excavation, it needs to be commissioned early enough to be issued before the application is lodged.

Regulation 14(p), printed page 17.
My house was approved under older byelaws. Am I now in violation?

Not on account of the change itself. Where a house or building has been constructed as per drawings approved under previous byelaws, rules or regulations which are contradictory to the present regulations, the violation may not be objected to and the completion certificate is issued accordingly. What governs is the edition in force when your drawing was approved.

Regulation 1(d), printed page 5.

Have Your Plot Checked Against the DHA Lahore Byelaws

Send these five things on WhatsApp and you will get a specific answer rather than a general one:

  1. Plot size — 5 Marla, 10 Marla, 1 Kanal, 2 Kanal or other
  2. Phase and block
  3. Plot dimensions in feet, for example 50 × 90
  4. Corner or non-corner. If corner, which side you intend to take as the frontage
  5. Where you are — no drawings yet, drawings in progress, ready to submit, submission returned, or a violation notice received

DHA decides every submission. Avenir’s role is to submit a compliant and complete drawing set, and to correct anything the Authority raises.

Typically replied to within working hours, Monday to Friday, 10:00–19:00 PKT.

Discuss My Project on WhatsApp Prefer a form? Fill the design brief instead